SD-02 Shop Drawings
Detailed Drawings[; G][; G, [_____]]
Detailed drawings, as specified.
Acceptance[; G][; G, [_____]]
Drawings which accurately depict the as-built configuration of
the installation, upon acceptance of the diesel-generator set
installation. Layout drawings shall be revised to reflect the
as-built conditions and shall be submitted with the as-built
drawings.
SD-03 Product Data
Performance Criteria
Calculations of the engine and generator output power
capability, including efficiency and parasitic load data.
Sound Limitations[; G][; G, [_____]]
Sound power level data for the packaged unit operating at 100%
load in a free field environment. The data should demonstrate
compliance with the sound limitation requirements of this
specification.
Engine-Generator Parameter Schedule
Description of the generator features which mitigate the effects
of the non-linear loads listed.
Integral Main Fuel Storage Tank
Day Tank
Calculations for the capacity of each day tank, including
allowances for recirculated fuel, usable tank capacity, and
Power Factor
The generator capability curve showing generator kVA output
capability (kW vs. kvar) for both leading and lagging power
factors ranging from 0 to 1.0.
Manufacturers data to quantify heat rejected to the space with
the engine generator set at rated capacity.
Cooling System
A letter which certifies that the engine-generator set and
specified, stating the following values:
a.
The maximum allowable inlet temperature of the coolant fluid.
SECTION 16263A
Page 10