Materials and Equipment
A certification stating that where materials or equipment are
specified to comply with requirements of UL, written proof of such
compliance has been obtained. The label or listing of the
specified agency, or a written certificate from an approved,
nationally recognized testing organization equipped to perform
such services, stating that the items have been tested and conform
to the requirements and testing methods of the specified agency
are acceptable as proof.
Inspections
A letter certifying that all facilities are complete and
functional; that each system is fully functional; and that each
item of equipment is complete, free from damage, adjusted, and
ready for beneficial use.
Cooling System
function properly in the ambient temperatures specified.
SD-10 Operation and Maintenance Data
[Six] [_____] copies of the operation manual (approved prior to
commencing onsite tests) in 215.9 x 279.4 mm (8-1/2 x 11 inch)
8-1/2 x 11 inch binders, having a minimum of 3 rings from which
material may readily be removed and replaced, including a separate
section for each system or subsystem. Sections shall be separated
by heavy plastic dividers with tabs which identify the material in
the section. Drawings shall be folded blue lines, with the title
block visible, and placed in 215.9 x 279.4 mm (8-1/2 x 11 inch)
8-1/2 x 11 inch plastic pockets with reinforced holes. One full
size reproducible mylar of each drawing shall accompany the
booklets. Mylars shall be rolled and placed in a heavy cardboard
tube with threaded caps on each end. The manual shall include:
step-by-step procedures for system startup, operation, and
shutdown; drawings, diagrams, and single-line schematics to
illustrate and define the electrical, mechanical, and hydraulic
systems together with their controls, alarms, and safety systems;
the manufacturer's name, model number, and a description of
equipment in the system. The instructions shall include
procedures for interface and interaction with related systems to
include [automatic transfer switches] [fire alarm/suppression
[_____]. Each booklet shall include a CDROM containing an ASCII
file of the procedures.
Maintenance Procedures[; G][; G, [_____]]
[Six] [_____] copies of the maintenance manual containing the
information described below in 215.9 x 279.4 mm (8-1/2 x 11 inch)
8-1/2 x 11 inch binders having a minimum of three rings from which
material may readily be removed and replaced, including a separate
section for each item listed. Each section shall be separated by
SECTION 16263A
Page 15