b.
The minimum allowable inlet temperature of the coolant fluid.
c. The maximum allowable temperature rise in the coolant fluid
through the engine.
Time-Delay on Alarms
The magnitude of monitored values which define alarm or action
set points, and the tolerance (plus and/or minus) at which the
devices activate the alarm or action for items contained within
the alarm panels.
Generator
Manufacturer's standard data for each generator (prototype data
at the specified rating or above is acceptable), listing the
following information:
a.
Direct-Axis subtransient reactance (per unit).
b. The generator kW rating and short circuit current capacity
(both symmetric and asymmetric).
Manufacturer's Catalog
Manufacturer's standard catalog data describing and depicting
each engine-generator set and all ancillary equipment in
sufficient detail to demonstrate complete specification compliance.
Site Welding
A copy of qualifying procedures and a list of names and
A letter listing the welder qualifying procedures for each
welder, complete with supporting data such as test procedures
used, what was tested to, and a list of the names of all welders
Spare Parts
List of spare parts, as specified.
Onsite Training
A letter giving the date proposed for conducting the onsite
training course, the agenda of instruction, a description of the
video taping service to be provided, and the kind and quality of
the tape to be left with the Contracting Officer at the end of the
instructional period.
Battery Charger
Battery charger sizing calculations.
Vibration-Isolation
Vibration isolation system performance data for the range of
frequencies generated by the engine-generator set during operation
SECTION 16263A
Page 11