USACE / NAVFAC / AFCESA
UFGS-16263A (December 2004)
---------------------------
Preparing Activity: USACE
Superseding
UFGS-16263A (June 2002)
UNIFIED FACILITIES GUIDE SPECIFICATIONS
References are in agreement with UMRL dated 23 June 2005
Latest change indicated by CHG tags
**************************************************************************
SECTION 16263A
DIESEL-GENERATOR SET STATIONARY 100-2500 KW, WITH AUXILIARIES
12/04
**************************************************************************
NOTE: This guide specification covers the
requirements for stationary diesel-driven generator
sets in the 100 to 2500 kilowatt capacity.
Comments and suggestions on this guide specification
are welcome and should be directed to the technical
proponent of the specification. A listing of
technical proponents, including their organization
designation and telephone number, is on the Internet.
Recommended changes to a UFGS should be submitted as
a Criteria Change Request (CCR).
Use of electronic communication is encouraged.
Brackets are used in the text to indicate designer
choices or locations where text must be supplied by
the designer.
**************************************************************************
PART 1
GENERAL
**************************************************************************
NOTE: This Specification is not for Procurement of
Gas-fueled Engine-generator Sets.
Transient-load-response performance characteristics
of natural gas, digester gas, propane, and liquefied
petroleum gas engines differ significantly from
differences. Consult manufacturers for sample
specifications.
Select the features and fill in blanks with values
appropriate for the design condition. This
specification does not apply to 400 Hz applications.
**************************************************************************
SECTION 16263A
Page 5