Functional Performance Test Checklist - Variable Volume Air Handling Unit
For Air Handling Unit: [_____]
_____________________________________________________________________________
d.
Unoccupied mode of operation
(1)
All dampers in normal position.
_____________________________
(2) Verify low limit space temperature is maintained as specified
in sequence of operation.
________________________________________________
e. The following shall be verified when the [supply fan off] [supply
and return fans off] mode is initiated:
(1)
All dampers in normal position.
_____________________________
(2)
All valves in normal position.
______________________________
(3)
Fan de-energizes.
___________________________________________
f. Verify the chilled water coil control valve operation by setting
all VAV's to maximum and minimum cooling.
Max cooling Min cooling
Supply air volume (_____ L/s)
__________
___________
Supply air temp.
(_____ degrees C)
__________
___________
Max cooling Min cooling
Supply air volume
_____ cfm)
__________
___________
Supply air temp.
(_____ degrees F)
__________
___________
g.
Verify safety shut down initiated by smoke detectors.
____________
h. Verify safety shut down initiated by low temperature protection
thermostat. ________________________________________________________________
2. Certification: We the undersigned have witnessed the above functional
performance tests and certify that the item tested has met the performance
requirements in this section of the specifications.
Signature and Date
Contractor's Chief Quality Control Representative
_____________________________
Contractor's Mechanical Representative
_____________________________
Contractor's Electrical Representative
_____________________________
Contractor's Testing, Adjusting and Balancing Representative
_____________________________
Contractor's Controls Representative
_____________________________
SECTION 15995A
Page 43