Functional Performance Test Checklist - Variable Volume Air Handling Unit
For Air Handling Unit: [_____]
Contracting Officer's Representative
_____________________________
Using Agency's Representative
_____________________________
Functional Performance Test Checklist - Single Zone Air Handling Unit
For Air Handling Unit:
[_____]
1. Functional Performance Test: Contractor shall verify operation of air
handling unit as per specification including the following:
a. The following shall be verified when the [supply fan operating]
[supply and return fans operating] mode is initiated:
(1)
All dampers in normal position. ______________________________
(2)
All valves in normal position.
______________________________
(3) System safeties allow start if safety conditions are met. _____
b.
Occupied mode of operation - economizer de-energized.
(1)
Outside air damper at minimum position. ______________________
(2)
Return air damper open. ______________________________________
(3)
Relief air damper [at minimum position] [closed]. ____________
(4) Chilled water control valve modulating to maintain space
cooling temperature set point. _____________________________________________
(5) Hot water control valve modulating to maintain space heating
temperature set point input from outside air temperature controller. ________
c.
Occupied mode of operation - economizer energized.
(1) Outside air damper modulated to maintain mixed air temperature
set point. _________________________________________________________________
(2) Relief air damper modulates with outside air damper according
to sequence of operation.
________________________________________________
(3) Chilled water control valve modulating to maintain space
cooling temperature set point. _____________________________________________
d.
Unoccupied mode of operation
(1) All dampers in normal position.
______________________________
(2) Verify low limit space temperature is maintained as specified
in sequence of operation. __________________________________________________
e. The following shall be verified when the [supply fan off] [supply
and return fans off] mode is initiated: