e.
Site elevation:
[_____] meters feet
f.
Ambient air temperatures:
(1)
Minimum:
[_____] degrees C F
(2)
Maximum:
[_____] degrees C F
g.
Maximum continuous output (steam):
[_____] kg/sec lb/hr
h.
Minimum continuous output (steam):
[_____] kg/sec lb/hr (without
smoking)
i.
Continuous blowdown:
[_____] percent
**************************************************************************
NOTE: Regarding the text below, the specified
efficiency for the boiler at maximum continuous load
shall be not less than 80 percent for coal and 82
percent for oil. If an economizer is used, use 82
and 84 percent respectively for coal and oil firing.
Depending on the particular application and fuel
used, these efficiencies could be higher.
**************************************************************************
j.
Efficiency at maximum continuous rating [includes economizer]
(1)
Coal:
[_____] percent
(2)
[Oil]:
[_____] percent
1.4.1.2
Economizer
**************************************************************************
NOTE: Economizers shall be specified for all
(gage) 50 psig and a capacity of 2 1/4 kg/sec 18,000
pounds per hour and larger. For boilers from 1/2 to
2/14 kg/sec 4,000 to 18,000 pounds per hour the
designer shall make the decision based upon a
specific economic analysis. This paragraph shall be
included as applicable.
**************************************************************************
**************************************************************************
NOTE: Unless a coal or a fuel oil to be burned has
an uncommon tendency to foul tubes, finned tube
economizers should be suitable for both fuels.
Feedwater temperatures should be 110 degrees C 230
degrees F when sulphur (S) content of oil is 0.5
percent; 116 degrees C 240 degrees F, S=1.5 percent
- 2 percent; 121 degrees C 250 degrees F, S=2.0
percent - 2.7 percent. Where fuels having more than
1.5 percent sulfur content are to be fired, finned
tubes shall not be used unless they are steel tubes
**************************************************************************
a.
Design pressure:
[_____] kPa (gage) psig
SECTION 15501N