than sizes indicated, the cost of providing additional electrical service
and related work shall be included under this section.
1.5
SAFETY
The Contractor shall ensure that employees are trained in the requirements
of OSHA 29 CFR 1910.1200 and understand the information contained in the
MSDS for protection against toxic and hazardous chemical effects.
PART 2
PRODUCTS
2.1
Drainage, waste, and vent pipe and fittings shall be as specified in
Section 15400 PLUMBING SYSTEMS.
2.2
WATER PIPING
Hot and cold water pipe and fittings shall be as specified in Section 15400
PLUMBING SYSTEMS.
2.3
INSULATION
Insulation shall be as specified in Section 15080 THERMAL INSULATION FOR
MECHANICAL SYSTEMS.
2.4
FIXTURES, FITTINGS, ACCESSORIES, AND SUPPLIES
**************************************************************************
NOTE: Mounting heights, clearances, access,
operating devices, insulation, and accessories for
hospital plumbing fixtures shall comply with Chapter
18, Provisions for the Physically Handicapped, in
Department of Defense Construction Criteria Manual
4270.1-M.
**************************************************************************
All products shall conform to the publications listed. Provide control
stop valves on each supply to each fixture. The finish of fittings,
accessories, and supplies exposed to view shall be chromium-plated. Fixture
fittings and trim shall conform to ASME A112.18.1M and ASME A112.19.5, as
applicable. Centerset faucets shall be top-mounted with inlets on not
greater than 100 mm 4 inch centers. Separate faucets and combination
supply fittings shall have inlets on 200 mm 8 inch centers. Zinc-alloy or
plastic handles will not be permitted for faucets and valves. [Provide
special roughing-in for wheelchair fixtures.] All fixture dimensions
specified are nominal.
2.4.1
Bath, Sitz (Item P0330)
ASME A112.19.2M, vitreous china, [wall] [pedestal] mounted sitz bath having
overall dimensions of 685 mm 27 inches long by 585 mm 23 inches wide with
height of back 535 mm 21 inches and height of rim 355 mm 14 inches to 405 mm
16 inches above the floor. Provide with water supply assembly, exposed
thermostatic mixing valve with thermometer, vacuum breaker, [attached water
supply] [1.50 meters5 feet of reinforced rubber hose and wall hook,]
[hand-held shower head] 40 mm 1 1/2 inch pop-up waste with operating
mechanism at the top of the fixture, [removable overflow] tailpiece with
adjustable cast brass P-trap, and integral overflow fitting.
SECTION 15411N