following the "G" typically are not used for Navy
projects.
Submittal items not designated with a "G" are
considered as being for information only for Army
projects and for Contractor Quality Control approval
for Navy projects.
**************************************************************************
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are [for Contractor Quality Control
approval.][for information only. When used, a designation following the
"G" designation identifies the office that will review the submittal for
the Government.] The following shall be submitted in accordance with
Section 01330 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Hospital plumbing fixtures
SD-03 Product Data
Fixtures
Fittings
Accessories
Supplies
SD-06 Test Reports
Submit field test reports as required in paragraph entitled
"Operational Test."
SD-08 Manufacturer's Instructions
Chlorination chemicals and other materials
SD-10 Operation and Maintenance Data
Hospital plumbing fixtures, Data Package 1
Submit in accordance with Section 01781 OPERATION AND
MAINTENANCE DATA.
1.4
ELECTRICAL MOTORS, CONTROLLERS, CONTACTORS, AND DISCONNECTS
**************************************************************************
NOTE: Use when electric motor driven equipment is
specified in this section.
**************************************************************************
Furnish motors, controllers, contactors, and disconnects with their
respective pieces of equipment. Controllers and contractors shall have a
maximum of 120-volt control circuits, and auxiliary contacts for use with
the controls furnished. When motors and equipment furnished are larger
SECTION 15411N
Page 6