Type and adjustment of drive [_____]
Capacity of tank [_____]
Electric motor:
Manufacturer, frame and type [_____]
Current characteristics and kW hp of motor [_____]
[_____] Thermal cut-out switch:
Manufacturer, type and
model [_____]
Starter:
Manufacturer:
Type and model [_____]
1.5
SAFETY PRECAUTIONS
1.5.1
Temperature Restriction
**************************************************************************
NOTE: The designer shall assure that the piping
design temperature is not exceeded, especially for
high temperature shutdown devices as required for
safe operation of the systems.
**************************************************************************
Compressors or other equipment shall not discharge compressed air to the
piping systems above [38] [_____] degrees C [100] [_____] degrees F unless
approved by the Contracting Officer. Aftercoolers or other devices shall
be provided to comply with the temperature restriction.
1.5.2
Rotating Equipment
Fully guard couplings, motor shafts, gears and other exposed rotating or
rapidly moving parts in accordance with OSHA 29 CFR 1910.219. Provide
rigid and suitably secured guard parts readily removable without
disassembling guarded unit.
1.5.3
Welding and Brazing
Safety in welding, cutting, and brazing of pipe shall conform to AWS Z49.1.
PART 2
PRODUCTS
2.1
LOW PRESSURE AIR COMPRESSOR, 7 1/2 TO 224 KW 10 TO 300 HP
**************************************************************************
NOTE: Prepare section for cooling water and include
in project specification. See Section 15181 for
piping and equipment which may be useful.
**************************************************************************
7 1/2 kW to 224 kW, up to 862 kPa (gage)10 to 300 hp, up to 125 psig.
Configuration and dimensions of the air compressor shall be compatible with
the indicated space allocated. Sound level shall not exceed 84 dBA one
data (paragraph 6.2) thereof:
SECTION 15211N