2.2.2
**************************************************************************
NOTE: Indicate finish colors of elevator materials
in finish schedule on drawings.
Use stainless steel door facing and side panels and
wall trim in hospital cars and for moist
environments such as humid or moist areas such as
hydroelectric plants, locks, and dams.
**************************************************************************
Provide finishes [as indicated.] [as listed below:
a. Floor; [mill finish steel diamond plate] [painted steel
diamond plate] [aluminum diamond plate] [tongue and groove
hardwood] [_____].
b. Walls; [prefinished steel panels] [stainless steel] [_____].
Wall trim; [prefinished steel] [stainless steel] [_____].
Accessories; [handrails] [_____].
c. Interior face of doors; [prefinished steel] [stainless steel]
[_____].
d. Ceiling; [prefinished steel panels] [stainless steel]
[anodized aluminum] [_____].
[e. Hoistway Doors and Frame Finishes; provide finishes on
exterior of hoistway as follows:
(1) Frame; [prefinished steel] [stainless steel] [_____].
(2) Exterior face of door; [prefinished steel] [stainless steel]
[_____].]]
2.3
SPECIAL OPERATION AND CONTROL
A17.1. Provide special operation key switches with [5] [6] pin cylinder
locks with removable cores. Provide a key control lock for each operation
system.
2.3.1
Firefighters' Service
**************************************************************************
NOTE: Firefighter Service is required on all
freight and passenger elevators. Coordinate the
Firefighters' designated floor level with the local
base Fire department and edit following paragraph
**************************************************************************
Provide equipment and signaling devices. The designated level for
Firefighters' key operated switch is the [ground] [____] floor.
2.3.2
Provide connections directly to elevator controls which will, when smoke is
detected by any smoke detector, actuate Firefighters' Service and send each
elevator to the correct floor as required by ASME A17.1. Provide
SECTION 14240
Page 15