1.3.3
Product Data Requirements
Include information on motor, hall station, and buffer on elevators and
accessories. For elevator supporting systems, include information on car
control[ and emergency power] systems, and for data sheets, provide
document identification number or bulletin number, published or copyrighted
prior to the date of contract bid opening.
1.3.4
Design Data:
Reaction Load Data Requirements
Provide calculations to the Contracting Officer for reaction loads imposed
on building by elevator system.[ Demonstrate calculations complying with
ASME A17.1, Appendix F.] Provide calculations certified by a licensed
structural engineer registered in any state. Do not fabricate materials
nor perform construction until approved by the Contracting Officer.
1.3.5
Certificates: Welders' Requirements
Comply with AWS D1.1/D1.1M, Section 5. Include certified copies of
welders' qualifications. List welders' names with corresponding code marks
to identify each welder's welding work.
1.4
NEW INSTALLATION SERVICE
**************************************************************************
NOTE: If elevator is located in remote location,
confirm the necessity for the 1 hour response time
required below with activity.
**************************************************************************
Provide routine warranty service in accord with the manufacturer's warranty
requirements, for a period of [12][_____] months after the date of
acceptance by Contracting Officer. [Perform this work during regular
working hours]. Include 24-hour emergency service, with 1 hour response
time, during this period without additional cost to the Government. Include
adjustments, greasing, oiling, and cleaning. Provide routine inspection
and tests of elevators in accordance with ASME A17.1 (Sections 1001 and
1002) and ASME A17.2.1. Provide supplies and parts to keep elevator system
in operation. Perform service only by factory trained personnel.
1.4.1
Special Operations
Every six months, test systems for[ Emergency Power Operation,][ Earthquake
Emergency Operation,][ Hospital Emergency Commandeering Service Operation][
and] Firefighters' Service. Schedule to not interfere with building
operations. For Frefighter's Service, test monthly in accordance with ASME
A17.1, Rule 1206.7. Deliver written results of each test operation to the
Contracting Officer.
1.4.2
Maintenance and Diagnostic Tools
Provide all special tools and software necessary to service and maintain
each elevator; deliver at time of final acceptance. Provide one of each
diagnostic tools unavailable on the open market. Include necessary
diagnostic tools are available on the open market.
SECTION 14210N
Page 8