Provide finishes [as indicated.][as listed below:
a.
Floor; [mill finish steel diamond plate][painted steel diamond
plate][aluminum diamond plate][tongue and groove hardwood][_____].
b.
Walls; [prefinished steel panels][stainless steel][_____].
Wall trim; [prefinished steel][stainless steel][_____].
Accessories; [handrail][_____].
c.
Interior face of doors; [prefinished steel][stainless
steel][_____].
d.
Ceiling; [prefinished steel panels][stainless steel][anodized
aluminum][_____].
e.
Provide finishes on exterior of hoistway as follows:
(1) Frame; [prefinished steel][stainless steel][_____].
(2). Exterior face of door; [prefinished steel][stainless
steel][_____].]
]2.2
SPECIAL OPERATION AND CONTROL
A17.1. Provide special operation key switches with [5][6] pin cylinder
locks with removable cores. Provide a key control lock for each operation
system.
2.2.1
Firefighters' Service
**************************************************************************
NOTE: Firefighters' Service is required on all
**************************************************************************
**************************************************************************
NOTE: Designer shall coordinate the firefighters'
designated floor level with the local base Fire
Department.
**************************************************************************
ASME A17.1, Section 211, Rule 211.3. Provide equipment and signaling
devices. The designated level for firefighters' key operated switch is the
[ground][____] floor.
2.2.2
Smoke Detectors
Smoke detectors are specified in [Section 13852, "Interior Fire Alarm
System"][____], including conduit and wiring from each detector to elevator
machinery space control panel. Provide connections directly to elevator
controls which will, when smoke is detected by any smoke detector, actuate
Firefighters' Service and send each elevator to the correct floor as
required by ASME A17.1. Provide dual-contact smoke detectors located in
the elevator lobbies and the elevator machine room. If sprinkler is
provided in the hoistway, provide dual-contact smoke detector at top of
SECTION 14210N
Page 12