all meters and controls required. The load tester shall be permitted to be
part of the radio alarm transmitter battery conditioner specified above.
2.12
SAFETY DISCONNECT SWITCH
Provide properly fused, safety-type disconnect switch and box with
provision for locking the cover and operating handle in the "power on"
position. Paint switch box "Fire Engine Red" and locate near the service
panel. Affix a permanent label reading "Fire Alarm Power" to each box.
Provide padlocks for locking the box cover and operating handle. Locks
provided shall be keyed alike. Switch boxes installed outdoors shall be
NEMA 3R type.
2.13
PROTECTED PREMISES CONTROL UNITS
**************************************************************************
necessary "dry" electrical contacts are available
for connection to the radio transmitter; if not, the
recommendations of its manufacturer or replaced.
Indicate on drawings which units require
modification or replacement under this contract and
include UFGS-13852, Interior Fire Detection and
Alarm System and/or UFGS-13855, Addressable
Interior Fire Detection and Alarm System, as
appropriate. Consult the EFD/EFA Fire Protection
Engineer for additional guidance as needed.
**************************************************************************
**************************************************************************
NOTE: Edit the following section to provide
connection to fire alarm control units (panels),
suppression system control units, extinguishing
system control units, and fire pump controllers, as
appropriate. If all suppression and extinguishing
system control units are connected to fire alarm
systems in compliance with the applicable NFPA
standards, separate connections between the
suppression/extinguishing system and the radio
transmitter are not required. If fire pump
controllers are connected to fire alarm systems in
such a way that the three separate alarm signals
required by NFPA 20 can be transmitted to the
fire/emergency communication center, separate
controller are not required.
**************************************************************************
**************************************************************************
NOTE: Indicate on the drawings the location of each
control unit, how many separate signals (circuits)
the designation of each circuit as it should be
annunciated at the communication center.
**************************************************************************
Fire alarm [and fire suppression/extinguishing system] control units [and
fire pump controller] alarm and supervisory contacts are [existing] [or]
SECTION 13853N
Page 30