(not counting unit number) or mouse clicks.
2.7.7
Pre-Incident Plan Retrieval
Provide system with pre-incident planning storage and retrieval capability.
The system shall enable the telecommunicator to access pre-incident plans.
For displayed alarm location, access to the pre-incident plan shall not
require more than two keystrokes or mouse clicks.
2.7.8
capability. The system shall enable the telecommunicator to access stored
hazardous material database information.
2.7.9
Power Source
Provide power for CAD system [through a connection into the line side of
the building's regular AC service circuit] [from the communication center
emergency service circuit] through a dedicated lockable fused disconnect
switch.
2.7.9.1
**************************************************************************
NOTE: Specify class of SEPSS based on requirements
of NFPA 1221 Chapter 2 and NFPA 72 Chapter 1. A
Class 0.25 SEPSS will provide power for 15 minutes,
and is the minimum allowable. A Class 4.0 SEPSS
will provide power for 4 hours, and is the minimum
recommended at locations not provided with emergency
**************************************************************************
Provide a Type U, Level 1, Class [0.25] [ 4.0 ] [____] Stored Emergency
Power Supply System (SEPSS) in compliance with NFPA 111. SEPSS shall
provide power for operation of CAD computer and monitor, and printer in the
event of loss of power on the line side of the SEPSS.
[2.8
INTERCONNECTION WITH EXISTING COMPUTER-AIDED DISPATCH (CAD) SYSTEM
**************************************************************************
NOTE: Use this paragraph if there is an existing
CAD system which is to be retained. Describe the
existing system as precisely as possible. Otherwise,
delete this paragraph.
**************************************************************************
2.8.1
Interconnection to Alarm Reporting System
Provide interconnection of radio alarm receiving/decoding networks with
existing CAD system so that alarms are automatically processed by the CAD
system, displayed on the CAD monitor screen, and printed on the CAD printer
as they are received. Existing CAD system utilizes [ _____ ] software,
version [ _____ ], and operates on a [ _____ ] computer with [ _____ ] MHz
processor, [ _____ ] hard drive, [ _____ ] RAM, [ _____ ] floppy disc
drive[, and [_____ ] CD ROM drive. [[ _____ ] ports are available for this
connection.]]
SECTION 13853N