IDS alarms [at two separate locations].
e.
Alarm reporting subsystem: Subsystem shall consist of electronic
devices to control, process, integrate, and annunciate IDS data
[at [two] [_____] separate locations].
f.
Power subsystem: Subsystem shall consist of components required
to ensure continuous operation of the entire IDS.
[2.2.1
Intrinsically Safe
**************************************************************************
NOTE: Do not locate control communicator within a
hazardous area. If point sensors and volumetric
sensors are required in hazardous areas, clearly
identify their location on the plans. Delete this
paragraph if no hazardous areas exist in this
project.
**************************************************************************
System components located in areas where fire or explosion hazards may
exist due to flammable gases or vapors, flammable liquids, combustible
dust, or ignitable fibers or flyings shall be rated and installed according
to Chapter 5 of NFPA 70. Classification of area and corresponding
equipment ratings and installation procedures shall be as defined and
specified in Chapter 5 of NFPA 70.
]2.3
INTEGRATED SYSTEM PERFORMANCE REQUIREMENTS
The installed and operating IDS shall be integrated into the overall
facility to detect intrusion and shall perform as an entity, as specified
below.
2.3.1
Detection Coverage
Provide and adjust sensors so that coverage is [overlapping and] maximized
without mutual interference. [IDS coverage shall include [the facility
perimeter] [and] critical spaces within the facility.]
2.3.2
Detection Resolution (Sensitivity)
Sensitivity shall be capable of the following:
a.
Locating intrusions at individually protected assets or at an
individual portal;
b.
Locating intrusions within volume/areas to within the coverage on
any single volumetric sensor; and
c.
Locating failures or tampering at individual sensors.
2.3.3
Detection Alarm and Reporting Capacity
**************************************************************************
NOTE: Select system capacity parameters based on
percent expansion factor to accommodate changes in
design caused by reconfiguration of equipment within
interior spaces or renovation.