2.1.4
Lock-down Encapsulant
Requirement
Test Standard
Flame Spread:
25, Smoke Emission - 50
ASTM E 84
Life Expectancy:
20 years
ASTM C 732 Accelerated
Aging Test
Permeability:
Minimum 0.4 perms
ASTM E 96
ASTM E 119
(Tested with fireproofing over encapsulant
applied directly to steel member)
Bond Strength: 1459 N of force/meter 100 pounds of force/foot
ASTM E
736
(Tests compatibility with cementitious and fibrous fireproofing)
PART 3
EXECUTION
3.1
EQUIPMENT
**************************************************************************
NOTE: Modify the number of sets of protective
equipment as required, depending on the size of the
asbestos removal project. Larger projects may
require more than two persons on an inspection team.
**************************************************************************
At all times, provide the Contracting Officer or the Contracting Officer's
Representative, with at least [two] [_____] complete sets of personal
protective equipment [including decontaminating reusable coveralls] as
required for entry to and inspection of the asbestos control area. Provide
equivalent training to the Contracting Officer or a designated
representative as provided to Contractor employees in the use of the
of compliance for all equipment used to contain airborne asbestos fibers.
3.1.1
Respirators
Select respirators from those approved by the National Institute for
Occupational Safety and Health (NIOSH), Department of Health and Human
Services.
3.1.1.1
Respirators for Handling Asbestos
Provide personnel engaged in pre-cleaning, cleanup, handling,
[encapsulation] [removal] [and] [or] [demolition] of asbestos materials
with respiratory protection as indicated in 29 CFR 1926.1101 and 29 CFR
1926.103.
3.1.2
Exterior Whole Body Protection
3.1.2.1
Provide personnel exposed to asbestos with disposable "non-breathable," [or