255.
NFPA 255 is also known as ASTM E 84.
NOTE: In accordance with NFPA 101, the use of
textile materials on walls and ceilings shall comply
with one of the following conditions:
a. Textile materials having a Class A rating
shall be permitted on the walls or ceilings of rooms
or areas protected by an approved automatic
sprinkler system.
b. Textile materials having a Class A rating
shall be permitted on partitions that do not exceed
3/4 of the floor-to-ceiling height or do not exceed
8 feet (2440 mm) in height whichever is less.
c. Textile materials having a Class A rating
shall be permitted to extend not more than 4 feet
(1200 mm) above the finished floor on ceiling-height
walls and ceiling-height partitions.
d. Textile materials shall be permitted on
walls and partitions where tested in accordance with
NFPA 265, Standard Methods of Fire Tests for
Evaluating Room Fire Growth Contribution of Textile
Wall Coverings. (ICC IBC, UBC 42-2 and UBC 8-2 are
equivalent to NFPA 265.)
**************************************************************************
Wallcoverings and accessories shall be material designed specifically for
the specified use. Vinyl wallcovering and borders shall be mercury,
cadmium, lead, and chromium free. Wallcoverings shall contain bactericides
and mildew inhibitors to protect against microbiological and mildew growth.
2.1.1
Vinyl Wallcovering [Type [A] [_____]]
**************************************************************************
NOTE: Select the appropriate vinyl Type designation
for each wallcovering specified and delete
inapplicable Types. Type selection should be based
on abuse conditions and the following
recommendations:
Type I (Light Duty) is satisfactory for use on
ceilings and light duty walls not subjected to
scuffing and abrasion. This type is rarely used.
Type II (Medium Duty) is satisfactory for areas
subject to average traffic wear and scuffing. It
may be used full height on walls or as a wainscot.
Type II should be used for most vinyl wallcovering
installations.
Type III (Heavy Duty) is slightly more resistant to
scuffing than Type II but is difficult to install
and clean, and is not available from most
manufacturers. Type III wallcovering is expensive
and should be used only where specifically requested.
Some manufacturer's Type I, Type II and/or Type III
wallcovering will overlap or vary slightly from the
weights shown in the following paragraphs.