Wallcoverings and Accessories[; G][; G, [_____]]
[Three] [_____] samples of each indicated type, pattern, and
color of wallcovering. Samples of wallcovering shall be minimum
125 x 175 mm 5 x 7 inches and of sufficient size to show pattern
repeat.
[Three][_____] samples of each indicated type of frame for
presentation dry erase wallcovering. Samples shall be a minimum
of 75 mm 3 inches long.
[Three] [_____] samples of each indicated type corner guard and
wainscot cap. Samples shall be a minimum of 75 mm 3 inches long.
Vinyl Wallcovering Mockup Panels. After vinyl wallcovering
samples are approved, and prior to starting installation, a
minimum 2430 x 2430 mm 8 x 8 foot vinyl wallcovering mock-up shall
be provided for each color and type of vinyl wallcovering, using
the proposed primers and adhesives and actual substrate materials.
Once approved, the mock-up samples shall be used as a standard of
workmanship for installation within the facility. At least 48
hours prior to mock-up installation, the Contractor shall submit
written notification to the Contracting Officer's Representative.
SD-07 Certificates
Wallcoverings and Accessories
Manufacturer's statement attesting that the product furnished
meets or exceeds specification requirements. The statement must;
be dated after the award of the contract, state Contractor's name
and address, name the project and location, and list the
requirements being certified.
SD-08 Manufacturer's Instructions
Wallcoverings and Accessories
accessories, adhesives and primers. Instructions shall include
preparation of the substrate.
SD-10 Operation and Maintenance Data
Wallcoverings[; G][; G, [_____]]
Submit Data Package 1 in accordance with Section 01781 OPERATION
AND MAINTENANCE DATA.
1.3
DELIVERY AND STORAGE
Deliver the material to the site in manufacturer's original wrappings and
packages and clearly label with the manufacturer's name, brand name,
pattern and color name and number, dye lot number, size, and other related
information. Store in a safe, dry, clean, and well-ventilated area at
temperatures not less than 10 degrees C 50 degrees F and within a relative
humidity range of 30 to 60 percent. Store wallcovering material in a flat
position and protect from damage, soiling, and moisture. Do not open
containers until needed for installation, unless verification inspection is