NOTE: 1. For tanks larger than 15,120 liters 4,000
gallons or for projects that have tanks, some of
which are smaller or larger than 15,120 liters 4,000
gallons, select the first optional paragraph and
include Section 13219, "Cleaning Petroleum Storage
Tanks."
2. For tanks 15,120 liters 4,000 gallonsand
smaller, select the second optional paragraph.
**************************************************************************
[Provide additional requirements for cleaning and vapor freeing tank as
specified in Section 13219 CLEANING PETROLEUM STORAGE TANKS.]
[Provide clean and vapor free tank in accordance with API RP 1604 and the
following:
a.
Table of Tank History
**************************************************************************
NOTE: Data for these paragraphs should be obtained
from the Commanding Officer of the individual Naval
facility having tanks for cleaning.
**************************************************************************
Tank
Tank
Tank
Date Con-
Type of Type of Remarks From
Number
Location
Capacity
structed
Lining
Fuel
the Last
(If Ap-
Inspection
plicable)
________________________________________________________________________
[_____]
[_____]
[_____]
[_____]
[_____]
[_____]
[_____]
[_____]
[_____]
[_____]
[_____]
[_____]
[_____]
[_____]
b.
Fuel Removal
**************************************************************************
NOTE: Contact the fuel department of the nearest
Naval Supply Center or Depot to determine if dirty
residual fuel can be accepted by the Government for
reclamation. If not reclaimed by the Government,
consider the following: Depending on the amount of
residual fuel remaining in the tank after pump down
by the Government and the degree of fuel
emulsification, the designer, in consultation with
the activity, should decide on whether to require
fuel/water separation under the scope of this
contract, dispose of the mixture as hazardous waste
if tests show presence of hazardous constituents, or
use other options available to the Government.
**************************************************************************
All possible fuel will be pumped or otherwise removed from the tank by the
Government. Consider remaining fuel contaminated or waste fuel; [pump into
208 liters 55 gallon drums or other suitable containers for disposal in
accordance with approved procedures meeting local, State, and Federal
regulations] [provide oil/water separators for further recovery of fuels
and turn over to the Government for use]. Dispose of remaining fuel
SECTION 02115N
Page 13