g. Interface definition.
1.3.5.3
Operator's Manual
The operator's manual shall fully explain all procedures and instructions
for operation of the system.
1.3.5.4
Maintenance Manual
The maintenance manual shall include descriptions of maintenance for all
equipment including inspection, periodic preventative maintenance, fault
diagnosis, and repair or replacement of defective components.
1.3.6
Group VI Technical Data Package
The Group VI Technical Data Package shall consist of the as-built drawings
revised to include system revisions and modifications. Copies of the
updated as-built drawings shall be delivered to the Government following
approval of the PVT and endurance test.
1.4
ENVIRONMENTAL REQUIREMENTS
**************************************************************************
NOTE: Select equipment and cable temperature
ratings within ambient temperature conditions at the
project location. State additional requirements
when ambient conditions are more extreme than
manufacturers' equipment ratings (e.g., conformal
atmospheres, enclosure heaters, or enclosure
coolers). The designer will show hazardous
(classified) environmental area(s), type of
hazard(s) and hazard classification (Class I, II, or
temperatures.) Whenever possible, avoid placement
of equipment and cables within the hazardous
location to reduce installation costs and to
simplify maintenance.
**************************************************************************
1.4.1
Indoor and Outdoor Environments
Equipment and cable to be used indoors shall be rated for continuous
122 degrees F dry bulb and 10 to 95 percent humidity, noncondensing.
Equipment and cable to be used outdoors shall be rated for continuous
degrees C minus 40 to plus 158 degrees F and humidity of up to 100 percent
condensing or as normally encountered for the installed location. All
equipment and cable shall be rated for continuous operation under the
ambient vibration conditions encountered for the installed location.
Cables installed in ducts, plenums, and other air-handling spaces shall be
installed per NEC. Cables installed in plenums shall be plenum-rated
cables listed for the use. Cables installed in risers shall be riser-rated
cables listed for the use, unless the installed cable is identified in the
NEC as a permitted substitution for the required riser-rated cable type.
Components located in areas where fire or explosion hazards may exist