any deficiency without written permission from the Government.
1.3.3
Group III Technical Data Package
The Contractor shall prepare test procedures and reports for the
predelivery test. The Contractor shall deliver the predelivery test
procedures to the Government for approval. After receipt by the Contractor
of written approval of the predelivery test procedures, the Contractor may
schedule the predelivery test. The final predelivery test report shall be
delivered after completion of the predelivery test.
1.3.4
Group IV Technical Data Package
The Group IV Technical Data Package shall include the following:
1.3.4.1
Performance Verification and Endurance Tests
**************************************************************************
NOTE: Insert Section number and title for the
appropriate specifications.
**************************************************************************
The Contractor shall prepare test procedures and reports in accordance with
Section [_____] for the performance verification test and the endurance
test. The test plan shall describe the applicable tests to be performed
and other pertinent information such as specialized test equipment
required, and length of performance verification test. The test procedures
shall explain in detail, step-by-step actions and expected results to
demonstrate compliance with the requirements of this specification. The
Contractor shall deliver the performance verification test and endurance
test procedures to the Government for approval. After receipt by the
Contractor of written approval of the test procedures, the Contractor may
schedule the tests. Coaxial cable is a low-impedance media, 50 or 75 ohms,
that is used in broadband applications. The required tests or acceptance
tests depend on the application and may include: DC loop resistance;
impedance; length; time domain reflectometer (TDR); attenuation; noise;
distortion; signal uniformity; signal-to-noise ration (SNR); bandwidth
signal ingress; and hum modulation. Generally, impedance, time domain, and
structural return loss tests are performed as a pre-installation check of
the cable. Tests for distortion, signal uniformity, bandwidth and SNR are
performed on installed cable using a signal level meter (SLM) unit. The
final performance verification and endurance test procedures report shall
be delivered after completion of the tests.
1.3.4.2
Group V Technical Data Package, shall be delivered to the Government prior
to beginning the performance verification test, for use during site
testing. Protocols and software for operation and maintenance of coaxial
cable modems shall be included in the manual.
1.3.4.3
Training Documentation
Lesson plans and training manuals for the training phases including type of
delivered for approval.