3.4.2
Contractor's Field Testing
**************************************************************************
NOTE: In item (a), include one or more of the
following UFGS for the appropriate video
transmission and signal and control transmission
media: Section 16792A WIRE LINE DATA TRANSMISSION
SYSTEM, Section 16768A FIBER OPTIC DATA TRANSMISSION
SYSTEM, or Section 16794A COAXIAL CABLE DATA
TRANSMISSION MEDIA.
**************************************************************************
The Contractor shall calibrate and test all equipment, verify DTM
operation, place the integrated system in service, and test the integrated
system. Ground rods installed by the Contractor shall be tested as
specified in IEEE Std 142. The Contractor shall deliver a report
describing results of functional tests, diagnostics, and calibrations
including written certification to the Government that the installed
complete system has been calibrated, tested, and is ready to begin
performance verification testing. The report shall also include a copy of
the approved performance verification test procedure. In addition, the
Contractor shall make a master video tape recording showing typical day and
night views of each camera in the system and shall deliver the tape with
the report. Note any objects in the field of view that might produce
highlights that could cause camera blinding. Note any objects in the field
of view or anomalies in the terrain which may cause blind spots. Note if a
camera cannot be aimed to cover the zone and exclude the rising or setting
sun from the picture. Note night assessment capabilities and whether
lights or vehicle headlights cause blooming or picture degradation. If any
of the above conditions or other conditions exist that cause picture
degradation or interfere with the camera field of view, the Contractor
shall inform the Contracting Officer. The tape shall be recorded using the
video recorder installed as part of the CCTV system. If a recorder is not
part of the CCTV system, the Contractor shall provide the tape in Video
Home System (VHS) format. The Contractor shall provide the Government with
the original tape as part of the documentation of the system and shall
submit a letter certifying that the CCTV system is ready for performance
verification testing. The field testing shall as a minimum include:
a.
Verification that the video transmission system and any signal or
control cabling have been installed, tested, and approved as
specified.
b.
When the system includes remote control/monitoring stations or
remote switch panels, verification that the remote devices are
functional, communicate with the security center, and perform all
functions as specified.
c.
Verification that the switcher is fully functional and that the
switcher software has been programmed as needed for the site
configuration.
d.
Verification that switcher software is functioning correctly.
All
software functions shall be exercised.
e.
Verification that video multiplexers are functioning correctly.
f.
Operation of all electrical and mechanical switcher controls and