AC power for all equipment shall be circuited to the emergency system
critical branch in accordance with NFPA 70 and NFPA 99.
3.4.2
Zone Lights
Zone lights shall be mounted and oriented in each corridor to assure that
the zone indicator lamps can be clearly seen anywhere in the corridor by
caregivers that need to respond to a call.
3.4.3
Installation Setup
Contractor shall make all adjustments and perform all application
programming as necessary to setup the system to function in accordance with
specific user requirements for the overall system and each patient care
area. Coordinate all such setup details with the medical facility users
prior to system commissioning, install them as part of the system setup,
and include the setup details in the O&M documentation. Examples of
installation setup details that require user coordination include the
following:
a.
Sound volume level for alert tone signals that have adjustable settings.
b.
Time and date setup.
c. Default call routing for patient care areas that have multiple master
stations.
d. Default settings for system networking, and for interfaces with the
medical facility Information System, Radio Paging System, and Wireless
Telephone System.
e. Preprogrammed pager and wireless phone service messages for each
patient care area.
f.
g.
Default pager and wireless phone listing and assignments.
h. Display layout configuration for systems that show a graphic
representation of the patient care area floor plan on each master station
monitor.
3.5
FIELD QUALITY CONTROL
3.5.1
Inspection, Checkout and Testing Services
a. Furnish required test equipment, tools, consumable supplies, and
technically qualified personnel to perform inspections, checkout and tests
of installed system.
b. Qualified NCAV System Contractor personnel conducting acceptance tests
shall be factory trained or certified and shall be completely knowledgeable
regarding the system application design, installation, and operation.
c. The Contracting Officer reserves the right to approve the system
Contractor's choice of testing personnel, and, upon rejection of any
testing personnel by the Contracting Officer at any time, the system
Contractor shall replace such testing personnel as soon as reasonably
possible. Upon request, the system Contractor shall provide the
SECTION 16731A
Page 57