[f. The NCAV System shall be interfaced with the Section 16730A NURSE CALL
TONE-VISUAL (NCTV) SYSTEM for call recording and reporting for the
specified NCTV system.]
2.7.3
Information System Server
a. Physical connection, protocol, and data communications as required for
interfacing with the medical facility Information System.
b. The server shall receive ADT information from the medical facility
Information System. The server shall provide any filtering of ADT data
required for use by the system.
c. The Information System Server shall be 100 percent compatible with the
interface requirements of the medical facility Information System.
2.7.4
Radio Page Server
a. Physical connection, protocol, and data communications as required for
interfacing with the Radio Paging System.
b.
Capacity for at least [____] pager addresses.
c. The Radio Page Server shall be 100 percent compatible with the input
requirements of the Radio Paging System CPU.
d. Calls shall be processed in accordance with the priority requirements
of the system, and forwarded to the Radio Paging System CPU with priority
level inputs as required by the CPU.
2.7.5
Wireless Telephone Server
a. Physical connection, protocol, and data communications as required for
interfacing with the messaging capability of the Wireless Telephone System.
b.
Capacity for at least [____] wireless phone numbers.
c. The Wireless Telephone Server shall be 100 percent compatible with the
input requirements of the Wireless Telephone System.
d. Calls shall be processed in accordance with the priority requirements
of the system, and forwarded to the Wireless Telephone System with priority
level inputs as required.
2.8
UPS
a. UPS shall be UL 1778 listed, and comply with the requirements of 47 CFR
15.
b. UPS Volt-Amp capacity shall be at least 130 percent of the total
volt-amp load of the equipment connected to the UPS. Power requirement
calculations shall be included with design data submittal to verify power
requirements.
c. Upon an ac power line outage, the UPS shall automatically transfer to
battery power within 4.2 milliseconds of sensing ac power line loss, and
provide at least 15 minutes of full power for operation of the equipment
connected to the UPS. On-battery output voltage shall be 115 VAC, +/- 5