consideration and the specifications adjusted
accordingly.
**************************************************************************
Equipment and materials furnished under this section shall be suitable for
the following unusual service conditions: altitude [_____] m feet, ambient
temperature [_____] degrees C F.
1.3.10
**************************************************************************
NOTE: Designer must identify hazardous areas and
show them on the drawings.
**************************************************************************
[Wiring shall conform to NFPA 70 for Class [I] [II] [III], Division [1] [2]
[operating temperature of [_____] degrees C F].] [Wiring and equipment
shall be of the classes, groups, divisions indicated, and suitable for the
indicated operating temperature.]
1.3.11
Protection of Security Lighting System Components
1.3.11.1
Components and Conductors
**************************************************************************
will be buried in areas where the likelihood of
damage to the conductors is slight. In areas where
subsurface utilities are congested and in areas
where the chance of accidental or intentional damage
conductors will be placed in ducts.
**************************************************************************
Security lighting system conductors shall be protected from damage.
Lighting system conductors shall be installed in raceways or by means of
direct burial, as shown. Where the conductors leave the underground
systems, the conductors shall be in rigid steel conduit of the indicated
size. Wire guards shall be provided to protect security lighting
luminaries mounted below 6.1 m 20 feet. A NEMA ICS 6, Type 4 enclosure
shall house exterior group-located electrical equipment such as time
switches, safety switches, and magnetic contactors. Where only one piece
of equipment is being provided at a location, the equipment shall be
provided with its own enclosure.
1.3.11.2
Tamper Provisions
**************************************************************************
NOTE: When an Intrusion Detection System (IDS) is
to be provided or is already in place, tamper
switches or welded covers are required. When an IDS
is not required, this paragraph will be deleted.
**************************************************************************
Enclosures, cabinets, housings (other than luminaire housings), boxes,
raceways, conduits, and fittings having hinged doors or removable covers,
and which contain any part of the security lighting system (including power
sources), shall be provided with corrosion-resistant tamper switches,
SECTION 16528A
Page 15