Transient voltage surge suppressors shall be provided for all electronic
equipment. Surge suppressors shall meet the requirements of IEEE C62.41,
and be UL listed as having been tested in accordance with UL 1449. Surge
suppressor ratings shall be [as indicated] [[_____] volts rms, operating
voltage; [50] [60] Hz; [1-phase] [3-phase]; [2] [3] [4] wire with ground;
transient suppression voltage (peak let-through-voltage) of [_____] volts].
Fuses shall not be used as surge suppression.
1.3.5
Interface CCTV Lighting and CCTV System
**************************************************************************
NOTE: Delete this paragraph if infrared lights are
not used for CCTV assessment.
**************************************************************************
Infrared lights shall be interfaced to the CCTV system and shall provide
automatic, alarm actuated call-up of the light associated with the alarm
zone.
1.3.6
**************************************************************************
NOTE: Include the secondary power panel only for a
backup generator as specified in another section.
The designer will determine the site requirements
**************************************************************************
Conductors shall [include all conductors extending from the load side of
the primary and secondary power panels that serve assessment lighting
equipment] [and] [be as indicated].
1.3.7
Nameplates
Each major component of equipment shall have a nonferrous metal or engraved
plastic nameplate which shall show, as a minimum, the manufacturer's name
and address, the catalog or style number, the electrical rating in volts,
and the capacity in amperes or watts.
1.3.8
Standard Products
Materials and equipment shall be standard products of manufacturer
regularly engaged in the manufacture of such products. Items of equipment
shall essentially duplicate equipment that has been in satisfactory use at
least 2 years prior to bid opening.
1.3.9
Unusual Service Conditions
**************************************************************************
NOTE: If normal service conditions prevail, omit
this subparagraph. Unusual service conditions for
altitude start above 1 kilometer (3300 feet) for
most apparatus. Ambient temperature is generally 40
degrees C, although in some cases 30 degrees C
applies. Frequency is generally 60 Hz, although 50
Hz may also be standard. Any unusual service
conditions or atmospheres shall be taken into