reach rated frequency and voltage and be ready to assume load within the
time specified. For standby sets used in emergency power applications,
each engine generator set will start, reach rated frequency and voltage,
and power will be supplied to the load terminals of the automatic transfer
switch within the starting time specified.
1.4.17
Experience
Each component manufacturer shall have a minimum of 3 years experience in
the manufacture, assembly and sale of components used with stationary
diesel engine-generator sets for commercial and industrial use. The
engine-generator set manufacturer/assembler shall have a minimum of 3 years
experience in the manufacture, assembly and sale of stationary diesel
engine-generator sets for commercial and industrial use.
1.4.18
Field Engineer
The engine-generator set manufacturer or assembler shall furnish a
qualified field engineer to supervise the complete installation of the
engine-generator set, assist in the performance of the onsite tests, and
instruct personnel as to the operational and maintenance features of the
equipment. The field engineer shall have attended the engine generator
manufacturer's training courses on installation and operation and
maintenance of engine generator sets.
1.4.19
Detailed Drawings
The Contractor shall submit detailed drawings showing the following:
a. Base-mounted equipment, complete with base and attachments,
including anchor bolt template and recommended clearances for
maintenance and operation.
b.
Complete starting system.
c.
d.
e.
f. Layout of relays, breakers, programmable
controllers,switchgear, and switches including applicable single
g. The complete lubrication system, including piping, pumps,
cooling,] [electric heater,] controls and wiring.
h. Location, type, and description of vibration isolation
devices for all applications.
i. The safety system, together with a detailed description of
how it is to work. Wiring schematics, safety devices with a
listing of their normal ranges, alarm and shutdown values (to
include operation parameters such as pressures, temperatures
voltages, currents, and speeds) shall be included.
SECTION 16263A