Delete the bracketed phrase if seismic details are
not provided. Sections 13080, 15070, and 16070,
properly edited, must be included in the contract
documents.
**************************************************************************
Seismic requirements shall be in accordance with Sections 13080 SEISMIC
PROTECTION FOR MISCELLANEOUS EQUIPMENT, 15070A SEISMIC PROTECTION FOR
MECHANICAL EQUIPMENT and 16070A SEISMIC PROTECTION FOR ELECTRICAL EQUIPMENT
[as shown on the drawings].
1.4.13
Fuel Consumption
**************************************************************************
NOTE: Delete this paragraph for standby
applications. For prime applications the designer
should discuss this requirement with the
installation to determine if it is required.
**************************************************************************
Engine fuel consumption shall not exceed the following maximum limits based
on the conditions listed below.
Size Range
% of Rated
Fuel Usage
Net kW
Output capacity
kg/kWH (lbs/kWH)
100 - 299
75 and 100
0.272 (0.600)
50
0.292 (0.643)
300 - 999
75 and 100
0.261 (0.575)
50
0.272 (0.600)
1000 - 2500
75 and 100
0.243 (0.536)
50
0.260 (0.573)
Size Range
% of Rated
Fuel Usage
Net kW
Output Capacity
LBS./kWH
100 - 299
75 and 100
0.600
50
0.643
300 - 999
75 and 100
0.575
50
0.600
1000 - 2500
75 and 100
0.536
50
0.573
Conditions:
a.
Net kW of the Set corrected for engine auxiliaries that are
electrically driven, where kW is electrical kilowatt hours.
b.
45 MJ/kg (19,350 Btu/pound) 19,350 Btu/pound high-heat value for
fuel used.
c.
Sea level operation.
d.
Intake-air temperature not over 32 degrees C 90 degrees F.
SECTION 16263A