projects located outside the continental United
States (OCONUS)
**************************************************************************
Perform and report on factory tests and inspections prior to shipment.
Provide certified copies of manufacturer's test data and results. Test
procedures shall conform to ASME, IEEE,[ IEC,] and ANSI standards, and to
ISO requirements on testing, as appropriate and applicable. The
consumables necessary for tests and measuring and indicating devices shall
be certified to be within calibration. Tests shall indicate satisfactory
operation and attainment of specified performance. If satisfactory,
equipment tested will be given a tentative approval. Equipment shall not
be shipped before approval of the factory test reports for the following
tests.
2.6.1
Engine Tests
Perform customary commercial factory tests in accordance with ISO 3046 on
each engine and associated engine protective device, including, but not
limited to the following:
a.
Perform dynamometer test at rated power. Record horsepower at rated
jacket water temperature, and ambient temperature.
b.
Test and record the values that the low oil pressure alarm and
protective shutdown devices actuate prior to assembly on the engine.
c.
Test and record values that the high jacket water temperature alarm and
protective shutdown devices actuate prior to assembly on the engine.
2.6.2
Generator Tests
**************************************************************************
NOTE: Include the bracketed option below for
projects located outside the continental United
States (OCONUS)
**************************************************************************
Tests shall be performed on the complete factory assembled generator prior
to shipment. Conduct tests in accordance with IEEE Std 115, NEMA C50.10[,
IEC 60034-2], and NEMA MG 1.
2.6.2.1
Routine Tests
Perform the following routine tests on the generators and their exciters:
a.
b.
Mechanical balance
c.
Phases sequence
d.
Open circuit saturation curve and phase (voltage) balance test
e.
Insulation resistance of armature and field windings
f.
High potential test
SECTION 16237N
Page 37