i.
Low dc voltage alarm relay
j.
High dc voltage alarm relay
k.
l.
2.2.6
Engine-Generator Control Panel
Provide NEMA ICS 6, Type[ 1][ _____], enclosed control panel mounted on the
engine-generator set with vibration isolators. Provide the following
control panel mounted devices and control features.
2.2.6.1
Control Panel Mounted Devices
a.
Engine Control Switch (ECS): Provide a three position control switch
with "MANUAL START" - "OFF/RESET" - "AUTO START" positions.
b.
Emergency Stop Push Button (ESPB): Provide a red, mushroom head,
twist-to-reset, maintained contact type push button.
c.
Generator Metering: Provide ac metering package that displays ac
voltage, current, and frequency of one phase of the generator output
simultaneously. Metering package shall include a voltmeter/ammeter
phase selector switch to allow viewing of each phase.
d.
Generator Voltage Adjust Potentiometer (VAP): Provide a potentiometer,
locking screwdriver type, to adjust generator voltage.
e.
the following engine information:
1.
Engine oil pressure
2.
Engine coolant temperature
3.
Engine speed (rpm)
4.
Engine running hours
f.
Indicating Lamps: Provide LED type indicating lamps and a lamp test
switch. Lamps shall indicate the following alarm and shutdown
conditions:
1.
2.
3.
High engine coolant temperature alarm
4.
High engine coolant temperature shutdown
5.
Engine overcrank shutdown
6.
Engine overspeed shutdown
7.
Emergency stop shutdown
SECTION 16237N