Functional Performance Test Checklist - Fan Coil Units
The Contracting Officer will select fan coil units to be spot-checked
during the functional performance test. The number of terminals shall not
exceed [2] [10] [10 percent].
1. Functional Performance Test: Contractor shall demonstrate operation of
selected fan coils as per specifications including the following:
a.
Cooling only fan coils:
(1) Verify fan coil unit response to room temperature set point
adjustment. Changes to be cooling set point to cooling set point minus 10
degrees and return to cooling set point. ___________________________________
(2)
Check blower fan air flow. _____ L/s
Check blower fan air flow. _____ cfm
(3)
Check cooling coil water flow. _____ L/s
Check cooling coil water flow. _____ gpm
(4)
Verify proper operation of cooling water control valve. ______
b.
Cooling/heating fan coils:
(1) Verify fan coil unit response to room temperature set point
adjustment. Changes to be cooling set point to heating set point and return
to cooling set point.
_____________________________________________
(2)
Check blower fan air flow.
_____ L/s
Check blower fan air flow.
_____ cfm
(3)
Check cooling coil water flow. _____ L/s
Check cooling coil water flow. _____ cfm
(4)
Verify proper operation of cooling water control valve.
_____
(5)
Check cooling mode inlet air temperature. _____ degrees C
Check cooling mode inlet air temperature. _____ degrees F
(6)
Check cooling mode outlet air temperature. _____ degrees C
Check cooling mode outlet air temperature. _____ degrees F
(7)
Check heating coil water flow.
_____ L/s
Check heating coil water flow.
_____ gpm
(8)
Verify proper operation of heating water control valve.
_____
(9)
Check heating mode inlet air temperature. _____ degrees C
Check heating mode inlet air temperature. _____ degrees F
(10)
Check heating mode outlet air temperature. _____ degrees C
Check heating mode outlet air temperature. _____ degrees F
2. Certification: We the undersigned have witnessed the above functional
performance tests and certify that the item tested has met the performance
requirements in this section of the specifications.
SECTION 15995A
Page 57