Functional Performance Test Checklist - Steam Boiler
For Boiler:
[_____]
1. Functional Performance Test: Contractor shall demonstrate operation of
steam heating system as per specifications including the following: Start
building heating equipment to provide load for boiler. Activate controls
system boiler start sequence as follows.
start sequence.
___________________________________________________________
b. Verify boiler senses steam pressure below set point and control
system activates boiler start.
____________________________________________
c. Shut off building heating equipment to remove load on steam heating
system. Verify boiler shutdown sequence is initiated and accomplished after
load is removed.
__________________________________________________________
d. Verify that water level and makeup water system are operational.
_____________________________________________________________________________
2. Verify boiler inlet/outlet pressure reading, compare to boiler design
conditions and manufacturer's performance data.
DESIGN
SYSTEM TEST
ACTUAL
Boiler inlet water temp (degrees F)
__________
__________
__________
Boiler outlet pressure (kPa gauge)
__________
__________
__________
Flue-gas temperature at boiler outlet (degrees C)
__________
__________
__________
__________
Draft at boiler flue-gas exit
__________
__________
Draft or pressure in furnace
__________
__________
Stack emission pollutants
_________
__________
__________
concentration
Fuel type
__________
__________
__________
__________
__________
__________
DESIGN
SYSTEM TEST
ACTUAL
Boiler inlet water temp (degrees F)
__________ __________
__________
Boiler outlet pressure (psig)
__________ __________
__________
Flue-gas temperature at boiler outlet (degrees F)
__________
__________
__________
__________
Draft at boiler flue-gas exit
__________
__________
Draft or pressure in furnace
__________
__________
Stack emission pollutants
__________ __________
__________
concentration
Fuel type
__________ __________
__________
__________ __________
__________
3.
Record the following information:
Ambient temperature __________ degrees C
Ambient temperature __________ degrees F
4.
Verify proper operation of boiler safeties.
__________________________
5.
Unusual vibration, noise, etc.
SECTION 15995A
Page 55