Functional Performance Test Checklist - Hot Water Boiler
For Boiler:
[_____]
1. Functional Performance Test: Contractor shall demonstrate operation of
hot water system as per specifications including the following: Start
building heating equipment to provide load for boiler. Activate controls
system boiler start sequence as follows.
a. Start hot water pump and establish hot water flow. Verify boiler
hot water proof-of-flow switch operation.
______________________________
b.
___________
c. Verify boiler senses hot water temperature below set point and
___________________________________
d. Shut off building heating equipment to remove load on hot water
system. Verify boiler shutdown sequence is initiated and accomplished after
load is removed.
_________________________________________________________
2. Verify boiler inlet/outlet pressure reading, compare to Test and
Balance (TAB) Report, boiler design conditions, and boiler manufacturer's
performance data.
DESIGN
SYSTEM TEST
ACTUAL
Boiler inlet pressure (kPa gauge)
__________ _________
__________
Boiler outlet pressure (kPa gauge)
__________ _________
__________
Boiler flow rate (L/s)
__________ _________
__________
Flue-gas temperature at boiler outlet
_________
__________
_________
__________
Draft at boiler flue-gas exit
_________
__________
Draft or pressure in furnace
_________
__________
Stack emission pollutants
__________ _________
__________
concentration
Fuel type
__________
_________
__________
__________
_________
__________
DESIGN
SYSTEM TEST
ACTUAL
Boiler inlet pressure (psig)
__________ _________
__________
Boiler outlet pressure (psig)
__________ _________
__________
Boiler flow rate (gpm)
__________ _________
__________
Flue-gas temperature at boiler outlet
_________
__________
_________
__________
Draft at boiler flue-gas exit
_________
__________
Draft or pressure in furnace
_________
__________
Stack emission pollutants
__________ _________
__________
concentration
Fuel type
__________
_________
__________
__________
_________
__________
3.
Record the following information:
Ambient temperature
__________ degrees C
Entering hot water temperature
__________ degrees C
Leaving hot water temperature
__________ degrees C
SECTION 15995A
Page 53