Functional Performance Test Checklist - Pumps
For Pump:
[_____]
Prior to performing this checklist, ensure that for closed loop systems,
system is pressurized and the make-up water system is operational or, for
open loop systems, that the sumps are filled to the proper level.
combination, on/auto, etc.).
ON__________
AUTO__________
OFF__________
a.
Verify pressure drop across strainer:
Strainer inlet pressure __________
kPa (_____ psig)
Strainer outlet pressure _________
kPa (_____ psig)
Strainer inlet pressure __________
psig
Strainer outlet pressure _________
psig
b. Verify pump inlet/outlet pressure reading, compare to Testing,
Adjusting, and Balancing (TAB) Report, pump design conditions, and pump
manufacturer's performance.
DESIGN
SYSTEM TEST
ACTUAL
Pump inlet pressure (kPa gauge) _________
__________
__________
Pump outlet pressure (kPa gauge) _________
__________
__________
DESIGN
SYSTEM TEST
ACTUAL
Pump inlet pressure (psig)
___________
__________
__________
Pump outlet pressure (psig)
___________
__________
__________
c. Operate pump at shutoff and at 100 percent of designed flow when
all components are in full flow. Plot test readings on pump curve and
SHUTOFF
100 percent
Pump inlet pressure (kPa gauge) __________
__________
Pump outlet pressure
__________
__________
Pump flow rate (L/s)
__________
__________
SHUTOFF
100 percent
Pump inlet pressure (psig)
__________
__________
Pump outlet pressure
__________
__________
Pump flow rate (gpm)
__________
__________
d. Operate pump at shutoff and at minimum flow or when all components
are in full by-pass. Plot test readings on pump curve and compare results
SHUTOFF
100 percent
Pump inlet pressure (kPa gauge) __________
__________
Pump outlet pressure
__________
__________
Pump flow rate (L/s)
__________
__________
SHUTOFF
100 percent
SECTION 15995A
Page 35