parts recommended by the manufacturer to be replaced after 1 year and 3
years of service. A list of special tools and test equipment required for
maintenance and testing of the products supplied by the Contractor shall be
included.
1.7
EXHAUST SYSTEM SPECIALIST
The Exhaust System Specialist shall perform work specified in this section.
The Exhaust System Specialist shall be regularly engaged in the
installation of the type and complexity of system specified in the Contract
documents, and shall have served in a similar capacity for at least three
systems that have performed in the manner intended for a period of not less
than 6 months.
PART 2
PRODUCTS
2.1
STANDARD PRODUCTS
Material and equipment shall be a standard product of a manufacturer
regularly engaged in the manufacture of the product and shall essentially
duplicate items that have been in satisfactory use for at least 2 years
prior to bid opening. Where an integrated, packaged exhaust system is
furnished, all items will be the product of the system manufacturer.
System component parts may be by other manufacturers. Equipment shall be
supported by a service organization that is capable of responding to
service calls within [four hours] [_____].
2.2
ASBESTOS PROHIBITION
Asbestos and asbestos-containing products shall not be used.
2.3
NAMEPLATES
All equipment shall have a nameplate that identifies the manufacturer's
name, address, type or style, model or serial number, and catalog number.
2.4
EQUIPMENT GUARDS AND ACCESS
**************************************************************************
NOTE: Catwalks, ladders, and guardrails may be
required. If so, select the applicable item and
indicate on drawings. If not applicable, delete the
entire sentence.
**************************************************************************
Belts, pulleys, chains, gears, couplings, projecting setscrews, keys, and
other rotating parts exposed to personnel contact shall be fully enclosed
or guarded according to OSHA requirements. High temperature equipment and
piping exposed to contact by personnel or where it creates a potential fire
hazard shall be properly guarded or covered with insulation of a type
specified. [Catwalks,] [operating platforms,] [ladders,] [and]
[guardrails] shall be provided where shown and shall be constructed
according to Section 05500A MISCELLANEOUS METAL.
2.5
CONTROLS
Controls shall be provided as specified in Section 15951 DIRECT DIGITAL
CONTROL FOR HVAC AND OTHER LOCAL BUILDING SYSTEMS.
SECTION 15940A
Page 9