made, and final test results.
SD-07 Certificates
Installation Drawings[; G][; G, [_____]]
Concurrent with installation drawings, manufacturer's
certification of installation drawings.
SD-10 Operation and Maintenance Data
[Six] [_____] manuals listing step-by-step procedures required
for system startup, operation, shutdown, cleaning, and routine
maintenance, at least 2 weeks prior to field training. The
manuals shall include the manufacturer's name, model number, parts
list, list of parts and tools that should be kept in stock by the
owner for routine maintenance including the name of a local
supplier, simplified wiring and controls diagrams, troubleshooting
guide, and Service Organization (including address and telephone
number) for each item of equipment.
1.6
QUALIFICATIONS
1.6.1
Manufacturer's Representative
Work specified in this section shall be performed under the supervision of
and certified by the Manufacturer's Representative. Certification shall be
provided for installation drawings, test procedures, and test results. The
Manufacturer's Representative shall have no less than 3 continuous years of
experience directly involved in the design and installation of evaporative
cooling systems, and shall have served in a similar capacity on no fewer
than five projects of similar size and scope during that period.
1.6.2
Service Organization
Work specified in this section shall be performed by a service organization
certified by the System Manufacturer. The Service Organization shall have
no less than 3 continuous years of experience directly involved in the
shall have served in a similar capacity on no fewer than five projects of
similar size and scope during that period. The Service Organization
submitted shall be capable of performing all maintenance and field repairs
and providing [4] [_____] hour onsite response to a service call on an
emergency basis.
PART 2
PRODUCTS
2.1
STANDARD PRODUCTS
The evaporative cooling systems shall be designed and assembled by a
manufacturer regularly engaged in the manufacturing of systems that are of
a similar design, workmanship, capacity, and operation. Systems of similar
design and capacity shall have been in satisfactory commercial or
industrial use for 2 years before bid opening. The 2 years must be
satisfactorily completed by a system which has been sold or is offered for
sale on the commercial market through advertisements, manufacturers'
catalogs, or brochures. Systems having less than a 2-year field service
SECTION 15690A
Page 8