projects, a code of up to three characters within
the submittal tags may be used following the "G"
designation to indicate the approving authority.
Codes for Army projects using the Resident
Management System (RMS) are: "AE" for
Architect-Engineer; "DO" for District Office
(Engineering Division or other organization in the
District Office); "AO" for Area Office; "RO" for
Resident Office; and "PO" for Project Office. Codes
following the "G" typically are not used for Navy
projects.
Submittal items not designated with a "G" are
considered as being for information only for Army
projects and for Contractor Quality Control approval
for Navy projects.
**************************************************************************
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for [Contractor Quality Control
approval.] [information only. When used, a designation following the "G"
designation identifies the office that will review the submittal for the
Government.] The following shall be submitted in accordance with Section
01330 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Piping Installation
Installation
installation details and electrical connection diagrams;
combustion and safety control diagrams; ductwork layout showing
the location of supports and hangers, typical hanger details,
gauge reinforcement, reinforcement spacing rigidity
classification, and static pressure and seal classifications; and
piping layout showing the location of guides and anchors, the load
imposed on each support or anchor (not required for radiant floor
tubing), and typical support details. Drawings shall include any
coordinated and will properly function as a unit and shall show
equipment relationship to other parts of the work, including
clearances required for operation and maintenance.
SD-03 Product Data
Materials and Equipment
Manufacturer's catalog data shall be included with the detail
drawings for the following items:
Unit Heaters
Fuel Burning Equipment
Pumps
Fittings and Accessories
Fuel Oil Storage System
Water Treatment System
SECTION 15569A
Page 12