Backflow preventer
SD-10 Operation and Maintenance Data
Submit in accordance with Section 01781 OPERATION AND
MAINTENANCE DATA.
SD-11 Closeout Submittals
Submit text for each piece of equipment.
1.6
QUALITY ASSURANCE
Equipment shall be factory assembled except for steam generators, coal
assembled components to the maximum extent to facilitate erection and
minimize field labor.
1.6.1
Standard Commercial Product
Boilers and equipment shall, as a minimum, be in accordance with
requirements of this specification and shall be the manufacturer's standard
commercial product. Include additional or higher quality features which
are not specifically prohibited by this specification, but which are a part
of the manufacturer's standard commercial product, in the boilers and
equipment being provided.
1.6.2
Equipment Furnished
Equipment furnished by the Contractor shall be furnished by the
manufacturers listed in the submittal letter listing equipment
manufacturers.
1.6.3
Responsibility
The contract drawings show the required general arrangement configuration
and location of equipment items. However, the contract allows for
selection of any vendor's equipment at the option of the Contractor,
provided the vendor's experience and equipment meet the requirements of
these specifications and drawings. Because there may be significant
variation between the drawings and the individual vendor's equipment as to
foundations, physical dimensions and detailed arrangement of equipment
items, the Contractor shall furnish detailed design and shop drawings and
calculations for the systems selected. Show foundation arrangements,
walkways and other information as required for a completely coordinated,
useable and properly functional system. A single system supplier shall be
responsible for a complete system including erection or erection
supervision for each of the following systems:
a.
Boiler system, including but not limited to the following:
Boiler, stoker, oil burners, [economizer], refractories,
insulation, induced draft fan, sootblowers, steam separator,
SECTION 15501N
Page 38