to demonstrate compliance with contract requirements. Performance
charts and curves shall provide performance data over the full
range of outdoor conditions for which dehumidification will be
required, with the conditions defined by the Contracting Officer.
Manufacturer shall supply data on all energy recovery methods and
procedures. If vibration isolation is specified for a unit,
vibration isolator literature shall be included containing catalog
cuts and certification that the isolation characteristics of the
isolators provided meet the manufacturer's recommendations.
Spare Parts
Spare parts data for each different item of material and
equipment specified.
Qualifications
operators, prior to non-factory welding operations.
Field Instructions
Posted instructions, at least 2 weeks prior to construction
completion, including equipment layout, wiring and control
diagrams, piping, valves and control sequences, and typed,
instructions shall include preventative maintenance procedures,
methods of checking the system for normal and safe operation, and
procedures for safely starting and stopping the system. The
posted instructions shall be framed under glass or laminated
plastic and be posted where indicated by the Contracting Officer.
Performance Tests
Test schedules, at least 2 weeks prior to the start of the field
tests and the system performance test. The schedules shall
identify the date, time, and location for the performance test.
Demonstrations
A schedule for training demonstrations, at least 2 weeks prior
to the date of the proposed training course, identifying the date,
time, and location for the training.
SD-06 Test Reports
Performance Tests[; G][; G, [_____]]
A report documenting the data taken versus the specified
performance criteria, upon completion of installation and
bound report (216 x 279 mm (8-1/2 x 11 inches) 8-1/2 x 11 inches)
shall be provided. The report shall document compliance with the
specified performance criteria upon completion and testing of the
system. The report shall indicate the number of days covered by
the tests and any conclusions as to the adequacy of the system.
SECTION 15500A
Page 6