1.3.2.3
Electrical Work
applicable requirements of Section 16402 INTERIOR DISTRIBUTION SYSTEM.
Electric motor-driven equipment specified herein shall be provided complete
with motors. Equipment shall be rated at 60 Hz, single phase, ac unless
otherwise indicated. Motors shall be open, dripproof type unless otherwise
indicated. Where a motor controller is not provided in a motor-control
center on the electrical drawings, a motor controller shall be provided
with the mechanical equipment. Electrical characteristics shall be as
sized thermal-overload protection in each ungrounded conductor, auxiliary
contact, and other equipment at the specified capacity including an
allowable service factor, and other appurtenances necessary for the motor
control specified. Manual or automatic control and protective or signal
devices required for operation herein specified and any wiring required to
such devices not shown on the electrical drawings shall be provided under
this section. Complete electrical schematic lineless or full line
interconnection and connection diagram for each piece of mechanical
equipment having more than one automatic or manual electrical control
device shall be submitted for approval. Manual or automatic control and
protective or signal devices required for operation herein specified and
any wiring required to such devices not shown on the electrical drawings
shall be provided under this section.
1.3.2.4
Medical Gas and Vacuum System Work
All work on medical gas and vacuum systems shall be in accordance with NFPA
99.
1.4
REGULATORY REQUIREMENTS
Unless otherwise required herein, plumbing work shall be in accordance with
ICC IPC.
1.5
PROJECT/SITE CONDITIONS
The Contractor shall become familiar with details of the work, verify
dimensions in the field, and advise the Contracting Officer of any
discrepancy before performing any work.
PART 2
PRODUCTS
2.1
MATERIALS
**************************************************************************
NOTE: Some materials listed are superior to others
for specific requirements. Therefore, information
should be obtained from the using service for any
special requirements before selection of material is
made. The type of tubing or pipe required will be
as determined by local experience. This
(15 inches) diameter only: designer will assure the
availability of materials when drainage line exceeds
425.0 mm (15 inches) diameter.
**************************************************************************
Materials for various services shall be in accordance with TABLES I and II.
SECTION 15405A
Page 22