c.
Refrigerant dryer and suction line strainer.
d.
Air-cooled condenser, with condenser fan and motor.
2.4.3
Include control panel in dryer cabinet containing:
a.
discharge air pressure gage, inlet air temperature gage, main
exchanger temperature gage, refrigeration compressor suction
green "Power On" light, power interruption light, and high
temperature light.
b.
Electrical Relays: Locate in an enclosed portion of the panel,
accessible for ease of servicing.
c.
point and to cycle air-cooled condenser with refrigeration
ambient temperature].
2.5
LOW PRESSURE COMPRESSED AIR DRYER (CHILLED WATER TYPE)
**************************************************************************
NOTE: Chilled water air dryers are usually provided
for 944 scms 2000 scfm and larger capacities.
CAUTION: Specify correct system pressure. If the
specification is edited to use a dryer with direct
heat exchange between air and refrigerant, assure
that the air is not used for breathing since
refrigerant leakage into the compressed air may be
hazardous to personnel; warning signs may be
required.
**************************************************************************
Provide low pressure compressed air dryer of the mechanical refrigerator
type, with closed chilled water system, regenerative air to air exchanger,
shall produce chilled water which, in turn, circulates through air-water
exchanger to dry the air. Provide internal tubing, wiring and piping
complete, such that only connections to air inlet and outlet, to pump
contactor, to refrigerant compressor contactor, to condensate drain, and to
air cooled condenser need be provided. Dryer shall be suitable for a
leaving temperature of [_____] degrees C F and dew point of [_____] degrees
C F at rated pressure.
2.5.1
Air Circuit
a.
passing through tubes and outlet air in shell, designed to reduce
cooling load at design conditions by precooling inlet air minus 7
degrees C 20 degrees F.
b.
Main Heat Exchanger: Shell and tube construction, single-pass,
with air in tubes and water in shell, designed for minimum air
pressure drop, flanged connections, tubes rolled into tube sheets,
SECTION 15211N
Page 18