2. Proper size of openings into hoistway walls for
installing hoistway door assemblies.
3. Storage facilities for elevator equipment during
construction.
4. Electrical service requirements for elevators,
including sizings in compliance with codes and
locations for fused and unfused disconnect switches.
5. Sill supports, including steel angles, sill
recesses, and grouting of door sills.
6. Structural steel door frames with extensions to
beams.
7.
Locations for hall stations and hall lanterns.
8. Emergency power supply with automatic time-delay
transfer switch and auxiliary contacts with wiring
to elevator controller.
9. Telephone and or Intercom connections to
elevator hoistway.
Firefighters' Service. The designer will also
indicate wiring of the smoke detectors to the
alarm system.
11. Wiring to elevator alarm bells and
fire-fighters' service.
12. Lighting, ventilation and heat to machine room.
Ambient temperature of 10 degrees C (50 degrees F)
min., 32 degrees C (90 degrees F) max.
**************************************************************************
1.1
REFERENCES
**************************************************************************
NOTE: Issue (date) of references included in
provided by the latest guide specification. Use of
SpecsIntact automated reference checking is
recommended for projects based on older guide
specifications.
**************************************************************************
The publications listed below form a part of this specification to the
extent referenced. The publications are referred to within the text by the
basic designation only.
AMERICAN WELDING SOCIETY (AWS)
AWS D1.1/D1.1M
(2004) Structural Welding Code - Steel
SECTION 14240
Page 6