entrance of insects or airborne materials. The screen shall not
inhibit the movement of smoke particles into the chamber.
d.
Provide twist lock bases for the sensors. The sensors shall
maintain contact with their bases without the use of springs.
conductor. Terminate field wiring on the screw terminals. The
sensor shall have a visual indicator to show actuation.
e.
The sensor address shall identify the particular unit, its
location within the system, and its sensitivity setting. Sensors
shall be of the low voltage type rated for use on a 24 VDC system.
f.
An operator at the control panel, having a proper access level,
shall have the capability to manually access the following
information for each initiating device.
(1)
Primary status
(2)
Device type
(3)
(4)
Present sensitivity selected
(5)
Sensor range (normal, dirty, etc.)
[2.2.6.2
Ionization Type Smoke Sensors
Provide addressable ionization type smoke sensors as follows:
a.
Provide analog smoke sensors which operate on the ionization
principle and are actuated by the presence of visible or invisible
products of combustion. Smoke sensors shall be listed for use
with the fire alarm control panel.
b.
Provide self-restoring type sensors which do not require any
readjustment after actuation at the FACP to restore them to normal
operation. Sensors shall be UL listed as smoke-automatic fire
sensors.
c.
Components shall be rust and corrosion resistant. Vibration shall
have no effect on the sensor's operation. Protect the detection
chamber with a fine mesh metallic screen which prevents the
entrance of insects or airborne materials. The screen shall not
inhibit the movement of smoke particles into the chamber.
d.
Provide twist lock bases for the sensors. The sensors shall
maintain contact with their bases without the use of springs.
conductor. Terminate field wiring on the screw terminals. The
sensor shall have a visual indicator to show actuation.
[e.
The sensor address shall identify the particular unit, its
location within the system, and its sensitivity setting. Sensors
shall be of the low voltage type rated for use on a 24 VDC system.]
f.
An operator at the control panel, having a proper access level,
shall have the capability to manually access the following
information for each initiating device.
(1)
Primary status
(2)
Device type
SECTION 13855N
Page 19