graphic annunciator]. [Indication on the graphic annunciator
shall be by floor, zone or circuit, and type of device.]
**************************************************************************
NOTE: Where a high-rise building in which the fire
alarm system is being provided is fully sprinkler
protected, the fire alarm notification appliances
should operate only on the fire floor, (one/two)
floor(s) above, and floor below. Where the building
has some fire protection or life safety concerns or
the building can be evacuated quickly, the fire
alarm system should operate all notification
appliances in the building upon a fire alarm. In
those buildings designed for total evacuation due to
fire protection or life safety concerns, design the
system so that it can easily be modified when the
fire protection or life safety improvements have
been made to the building.
**************************************************************************
(3) [Continuous actuation of all alarm notification appliances,
except those in stairs or in elevator cabs.] [Continuous
actuation of alarm notification appliances on the floor of fire
alarm origin, the floor above the floor of fire alarm origin, and
the floor below the floor of fire alarm origin, except those in
stairs or in elevator cabs.]
[(4)
Recording of the event via the system printer.]
[(5)
Release of doors held open by electromagnetic devices.]
system].]
[(7) Release of power to electric locks on doors which are part
of the means of egress.]
[(8) Operation of a smoke sensor in an elevator lobby or other
location associated with the automatic recall of elevators, shall
recall the elevators in addition to other requirements of this
paragraph.]
[(9) Operation of a duct smoke sensor shall shut down the
appropriate air handler in accordance with NFPA 90A in addition to
other requirements of this paragraph.]
**************************************************************************
NOTE: Use this paragraph only where a sensor or
detection system is to release a special fire
extinguishing system.
**************************************************************************
[(10) Operation of [_____] shall release the [_____] fire
extinguishing system after a [_____] second time delay.]
[(11) Operation of a sprinkler waterflow switch serving an
elevator machinery room shall operate shunt trip circuit
breaker(s) to shut down power to the elevators in accordance with
IEEE A17.1.]
SECTION 13855N
Page 16