proof of UL certification and a list of installer's personnel.]
For each system installed, submit the following:
a.
A detailed summary of the type and design of the system;
b.
The contract name or number, completion date of the project, and
total cost of the system;
c.
The name and telephone number of the facility or installation for
whom the work was performed; and
d.
The name and telephone number of a supervisory level point of
contact at the facility or installation who has knowledge of the
performance of the Contractor's or installer's work.
1.7.2
Manufacturer's Representative
**************************************************************************
NOTE: Consult with EFD's Fire Protection Engineer
for guidance on when to include the UL certified
requirements for the system installer.
**************************************************************************
Provide the services of a qualified manufacturer's representative or
technician, experienced in the installation and operation of the type of
system being provided to supervise the installation, testing (including
final testing), and adjustment of the system. [Ensure that the installer
is UL certified for the installation and testing of the fire alarm systems.
Provide proof of this listing. A list of installers personnel shall be
provided as part of the submittal package under the subparagraph titled
"SD-07, Certificates."]
[1.7.3
Qualifications of System Technician
**************************************************************************
NOTE: For projects administered by the
PACNAVFACENGCOMHQ, include the following paragraph
requiring the minimum qualification of a NICET
Level -III technician for preparation of all fire
protection system drawings.
**************************************************************************
Installation drawings, shop drawings, and as-built drawings shall be
prepared by, or under the supervision of, a qualified technician.
Qualified technician shall be an individual who is certified by the
National Institute for Certification in Engineering Technologies (NICET) as
an engineering technician with minimum Level III certification in fire
alarm system program. Contractor shall submit data showing the names and
certification of the technician at or prior to submittal of drawings.
]1.7.4
Regulatory Requirements
Materials and equipment for fire alarm service shall be listed UL Fire Prot
Dir or approved by FM P7825. Provide current materials and equipment of
one manufacturer regularly engaged in production of such equipment, and
provide items that have performed satisfactorily for at least 2 years prior
to bid opening.
SECTION 13854N