Power Calculations; G
SD-06 Test Reports
Preliminary Testing; G
Final Acceptance Test; G
Submit for inspections and tests specified under paragraph
titled "Field Quality Control."
SD-07 Certificates
[Qualifications of installer; G]
[Qualifications of system technician ; G]
Year 2000 (Y2K) Compliance Warranty; G
System UL Listing or FM Approval; G
SD-10 Operation and Maintenance Data
Digital alarm system, Data Package 5; G
Submit in accordance with Section 01781 OPERATION AND
MAINTENANCE DATA.
SD-11 Closeout Submittals
System As-built Drawings
1.7
QUALITY ASSURANCE
**************************************************************************
NOTE: Include "Qualifications of installer list of
prior installations" listed below, only for projects
administered by the PACNAVFACENGCOM.
**************************************************************************
1.7.1
Qualifications of Installer
**************************************************************************
NOTE: The experience clause in this guide
specification has been approved by a Level I
Contracting Officer and may be used without further
approval or request for waiver.
**************************************************************************
The Contractor or installer shall have satisfactorily installed fire alarm
reporting systems of the same type and design as specified herein [and
shall be UL certified for the installation and testing of fire alarm
systems].
Prior to commencing fire alarm reporting system work, submit data showing
that the Contractor or installer has satisfactorily installed three fire
alarm systems of the same type and design as specified herein within the
past 3 years[ and certify that each system has performed satisfactorily in
the manner intended for a period of not less than 18 months].[ Submit
SECTION 13854N
Page 8