projects, a code of up to three characters within
the submittal tags may be used following the "G"
designation to indicate the approving authority.
Codes for Army projects using the Resident
Management System (RMS) are: "AE" for
Architect-Engineer; "DO" for District Office
(Engineering Division or other organization in the
District Office); "AO" for Area Office; "RO" for
Resident Office; and "PO" for Project Office. Codes
following the "G" typically are not used for Navy
projects.
Submittal items not designated with a "G" are
considered as being for information only for Army
projects and for Contractor Quality Control approval
for Navy projects.
**************************************************************************
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are [for Contractor Quality Control
approval.][for information only. When used, a designation following the
"G" designation identifies the office that will review the submittal for
the Government.] The following shall be submitted in accordance with
Section 01330 SUBMITTAL PROCEDURES:
The fire protection engineer, [_____] Division, Naval Facilities
Engineering Command will review and approve all submittals in this section
requiring Government approval.
**************************************************************************
NOTE: For projects administered by Pacific
Division, NAVFACENGCOM, use the submittal paragraph
below in lieu of the above paragraph. Delete the
"G" after each submittal item, except under "SD-08
Statement."
**************************************************************************
The Pacific Division, Naval Facilities Engineer delegates the authority for
review and approval of all submittals required by this section to the U.S.
Registered Fire Protection Engineer employed in the Quality Control (QC)
Organization, specified under Section 01450N DESIGN AND CONSTRUCTION
QUALITY CONTROL. Submit to the Pacific Division, Naval Facilities
Engineering Command, Fire Protection Engineer two sets of all approved
submittals and drawings immediately after approval but no later than 15
working days prior to final inspection.
SD-02 Shop Drawings
[
Fire station; G]
[
Fire alarm headquarters; G]
[
Exterior fire alarm reporting and receiving system; G]
Submit detail plan showing the location of fire alarm equipment
diagrams shall show points of connection and terminals to be used,
completely indicate the function of the control panel and devices
SECTION 13851N