4. Location of the panel, bells, and other
equipment.
5.
Location of the alarm gongs and bells.
6.
Location of all boxes.
7. All portions of the system that will be
underground and any portion that will be installed
in an outside overhead system.
8. Cables that are to be installed in the
duct-and-manhole system, the design of the system,
the location of the cables, and the number of
conductors in each cable.
9. Cables that are to be installed in outside
overhead systems, the design of the system, the
location of the cables, and the number of conductors
in each cable.
10. Cables that are to be buried directly in earth,
their location, where cables pass under roadways or
paved areas, and the ducts or conduits used, and the
number and AWG size of conductors in each cable.
11. Locations of the branch or "Y" connections and
the necessary related details.
12. Ground connections that should be welded or
brazed, if any.
arrangement.
14.
System timing.
15. Code Numbers of Fire Alarm Boxes: Coding shall
be an integrated four-digit code. Code numbers
should not contain any digit larger than 6, shall
not have succeeding digits of the number "1" or "0."
(Example: 1-1-3-4.) A table should indicate
location of all boxes with respective code numbers.
**************************************************************************
PART 1
GENERAL
1.1
REFERENCES
**************************************************************************
NOTE: Issue (date) of references included in
provided by the latest guide specification. Use of
SpecsIntact automated reference checking is
recommended for projects based on older guide
specifications.
**************************************************************************
The publications listed below form a part of this specification to the
SECTION 13851N
Page 5