shall be supervised by the system. The system shall supervise the signal
lines by monitoring changes in the direct current that flows through the
signal lines and a terminating resistor. The system shall initiate an
alarm in response to a current change of [5] [10] percent or greater. The
system shall also initiate an alarm in response to opening, closing,
shorting, or grounding of the signal and DTS lines.
1.5.2
Data Encryption
**************************************************************************
NOTE: Data encryption should be used only when
been determined that it is undesirable to allow
unauthorized persons access to system
intercommunication.
**************************************************************************
on data transmission media links as shown. The algorithm used for
encryption shall be the Data Encryption Standard (DES) algorithm described
in ANSI INCITS 92.
1.6
DATA TRANSMISSION SYSTEM (DTS)
**************************************************************************
NOTE: The designer will include in the project
specification the UFGS specified below.
**************************************************************************
The Contractor shall provide data transmission systems as specified in
Section 16792A WIRE LINE DATA TRANSMISSION SYSTEM and as shown.
1.7
EXPERIENCE
The Contractor shall submit written proof that the following experience
requirements are being met.
1.7.1
Hardware Manufacturer
All system components shall be produced by manufacturers who have been
regularly engaged in the production of intrusion detection system
components of the types to be installed for at least 3 years.
1.7.2
Software Manufacturer
All system and application software shall be produced by manufacturers who
and application software of similar type and complexity as the specified
system for at least 2 years.
1.7.3
System Installer
The system shall be installed by a contractor who has been regularly
and complexity as the specified system for at least 2 years.
SECTION 13721A